Introduction to Basic Ladder Logic Instructions
| |
Introduction to Basic Ladder Logic Instructions
|
Introduction
In this section we will cover the
count up count down and reset instruction. Counters are
very essential in ladder logic programming. Counters are
used to index, increment or decrement values.
Definition
The following is a list of counter
instructions in SLC 500:
- CTU - Count Up
- CTD - Count Down
- RES - Reset
CTU Count UP
Symbol

Definition
- Increments the accumulated value
at each false to true transition and retains the
accumulated value when the instruction goes false or
when power cycle occurs.
- The CTU is an instruction that
counts false to true transition. When this
transition happens the accumulated value is
incremented by one count.
- A CTU accumulation is reset by
the RES instruction.
- If the accumulation value is over
the maximum range then the overflow (OV) bit will be
true.
Each counter address is made of a
3-word element.
Word 1 is the control word
- Bit 0-7: Internal Use
- Bit 10: UA - Update accumulation
value.
- Bit 11: UN - Underflow bit.
- Bit 12: OV - Overflow bit.
- Bit 13: DN - Done
- Bit 14: CD - Count down is
enabled.
- Bit 15: CU - Count up is enabled.
Word 2 stores the preset value. (PRE)
- Specifies the value, which the
counter must reach before the controller sets the
done bit. When the accumulator value becomes equal
to or greater than the preset value, the done status
bit is set. You can use this bit to control an
output device.
- Preset value is from -32,768 to
32,767
- If a timer-preset value is
negative an error will occur.
Word 3 stores the accumulated value. (ACC)
- This is the number of times of
false to true transitions that have occurred since
the counter was last rest.
CTD Count Down
Symbol

Definition
- Decrements the accumulate value
at each false to true transition and retains the
accumulated value when the instruction goes false or
when power cycle occurs.
- The CTD is an instruction that
counts false to true transition. When this
transition happen the accumulated value is
decrements by one count.
- A CTD accumulation is reset by
the RES instruction.
- If the accumulation value is
below the minimum range then the underflow (UN) bit
will be true.
· Each counter address is made of a
3-word element.
Word 1 is the control word
- Bit 0-7: Internal Use
- Bit 10: UA - Update accumulation
value.
- Bit 11: UN - Underflow bit.
- Bit 12: OV - Overflow bit.
- Bit 13: DN - Done
- Bit 14: CD - Count down is
enabled.
- Bit 15: CU - Count up is enabled.
Word 2 stores the preset value. (PRE)
- Specifies the value, which the
counter must reach before the controller sets the
done bit. When the accumulator value becomes equal
to or greater than the preset value, the done status
bit is set. You can use this bit to control an
output device.
- Preset value is from -32,768 to
32,767
- If a timer-preset value is
negative an error will occur.
· Word 3 stores the accumulated value. (ACC)
RES Reset
Symbol

Definition
- Resets the accumulated value and
status bit of a timer or counter.
- Use a RES instruction to reset
timers or counters. When the RES instruction is
enabled, it resets the Timer On Delay, Retentive
Timer, and Counter Up, Counter Down instruction
having the same address as the RES instruction.
Links
|
|
©2007-2020 Intro2U.COM. All
rights reserved. Intro2U.COM and its Contents are registered trademarks of
Intro2U.COM
The Introduction Search Engine, The Introduction Web, The Introduction Toolbar
and Design Info are service marks of Intro2U.COM
No portion of this site may be copied, retransmitted, reposted, duplicated or
otherwise used
without the express written permission of Intro2U.COM
|